Operating Manual


Strainer ClearingStrainer Clearing
During operation of the unit it may become necessary to clear the strainer of grass or debris from the water source. This is easily performed and should only take 15 to 30 seconds.

Discontinue water supply operations by closing down all discharges from the truck except for the line supplying the TurboDraft unit.

Open the tank-to-pump valve.

Slowly close the suction intake valve. This will cause the flow of water to backup into the strainer and clear any obstructions from the screen.

Keep valve closed for 15 to 30 seconds to ensure the debris is cleared from the strainer area.

Slowly open the suction intake valve to re-establish the water supply.

Close tank-to-pump valve and open tank fill valve 1/4 to 1/2 and refill tank.

When tank is full, close tank fill valve and resume flow operations.

 